8-5
Overshoot : ±1% of full scale
1. The analog output is received through a twisted pair shield cable. This cable should be wired separately from power line or
any other lines which may induce electrical noise.
*No need for this device to be verified by the factory, and should any problem occurred, please return this device to the original
factory or the agent.
External Wiring Example Diagram
CH0
CH1
V+
V-
V+
V-
Inverter
Shielded
*If the external wiring is not conducted properly, erroneous motions or damages might result, and consequently, if there is the
condition of short-circuits for the analog voltage output, it is then very likely that a permanent damage will take place.
Allowed type of loads: floating
Maximum capacitive load (for voltage outputs): 100PF
The responding time from the point where the power is supplied till an output signal is generated: 4 sec
Output ripple: less than 0.1%