Cable Electronics DVP14 Specifiche Pagina 129

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 150
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 128
8. EX MPU and I/O Extension Units
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-4
*This unit may be damaged by input voltages in excess of ±15V or ±30mA.
*If the voltage or current exceeds ±15V or ±30mA during the operation, it will then result in permanent damage to this unit. Users
should pay special attention to avoid the above-mentioned incident.
Ϩʳ Digital/Analog (D/A)
Analog Output:
Monotonicity with no miss code
Overall Precision:
Non-linearity: ±1% of full scale over temperature.
Maximum error: ±1% of full scale of +10V and +20mA over temperature.
Data format returned to the application program: Binary.
Value of LSB (Least Significant Bit):
Voltage output: 78.125 mV
Current output: 78.125 µA
Total input system transfer time (TAID + TAIT) 2ms
Refresh time:0.5ms
Conversion time:0.5ms
Setting time for full range change = 1ms
0V
K0MCU
1ms0.5ms
K255
0.5ms
Analog Input
Refresh
Conversion
time
Setting
time
Vedere la pagina 128
1 2 ... 124 125 126 127 128 129 130 131 132 133 134 ... 149 150